• Check Stock
  • Language Icon
  • My Cart My Cart
  • Sign in

ATS-AIC-2080

*Image above is for illustration purpose only..
ATS-AIC-2080
AI Chip Coolers / DLC Cold Plate

The ATS-AIC-2080 is a compact, high-efficiency DLC cold plate designed for reliable thermal control in space-constrained systems. It delivers consistent heat removal with low pressure drop, making it well suited for high-density computing environments.

Features & Benefits
  • Designed for Intel Xeon Platinum 8592+ and Intel Xeon Max 9480 applications
  • Thermal resistance as low as 0.01 °C/W (at 5–6 LPM)
  • Up to 5 kW thermal design power capability
  • Precision copper construction for uniform heat removal
  • Compact dimensions: 76.6 × 99 × 29.1 mm
  • Cooling area: 56.5 × 72 mm
  • Weight: 620 g
  • Universal barb fittings for 8 mm OD / 5 mm ID tubing
Applications
  • AI training accelerators and high-power GPUs
  • Advanced HPC processors and computer platforms
  • High-density AI racks using direct-to-chip cooling
Specifications
Part Number Lifecycle
Status
Plate Dimension (mm) Weight (gr) Material Flow Rate
LPM(GPM) 1.0 (0.26)
Flow Rate
LPM(GPM) 2.0 (0.52)
Flow Rate
LPM(GPM) 3.0 (0.79)
Flow Rate
LPM(GPM) 4.0 (1.05)
Length Width Height R
(°C/W)
dP
kPA (psi)
R
(°C/W)
dP
kPA (psi)
R
(°C/W)
dP
kPA (psi)
R
(°C/W)
dP
kPA (psi)
ATS-AIC-2080 ACTIVE 76.6 99.0 29.1 620 Cu 0.016 3.52 (0.51) 0.014 12.48 (1.81) 0.012 27.65 (4.01) 0.012 48.26 (7.00)
Thermal Performance
Schematic Image Thermal Resistance
Flow Rate
LPM(GPM)
R
(°C/W)
dP
kPA (psi)

*Image above is for illustration purpose only.
1.0 (0.26) 0.016 3.52 (0.51)
2.0 (0.52) 0.014 12.48 (1.81)
3.0 (0.79) 0.012 27.65 (4.01)
4.0 (1.05) 0.012 48.26 (7.00)
5.0 (1.32) 0.011 71.02(10.3)
6.0 (1.58) 0.01 102.73(14.9)
ATS-AIC-2080    (Data Sheet)
download data sheet
ATS-AIC-2080
CAD MODEL (Fused Model) - use for Form and Fit
Download CAD Model (Fused Model) (used for Form and Fit use)
RoHS & REACH Certificate download data sheet
Complete Your Liquid Loop with ATS

ATS has the products needed to design a complete liquid cooling loop : iCDMs (Industrial Cooling Distribution Modules), Tubed and High Performance Cold Plates to transfer and remove the heat from the source; Heat Exchangers to transfer heat from the liquid to the air with or without a fan; Chillers to circulate and condition the fluid in the system, Compact Refrigeration Modules for very high capacity cooling. In addition , ATS offers Flow Meters to measure the volumetric flow rate of the fluid in the system and Leak Detectors to notify users of any leaks in the system.