AI Chip Coolers

The NIVIS Keld cold plate introduces copper-base construction for improved heat conduction while maintaining a manageable mass. Its internal structure is tuned for balanced flow and enhanced heat transfer across high-power AMD SP5 processors. Ideal for AI-training clusters, advanced servers and industrial cooling applications demanding higher conductivity.

Features & Benefits
  • Copper's superior thermal conductivity for demanding CPUs
  • Enhanced durability and stable thermal cycling performance
  • Maintains low pressure-drop for series/parallel cooling loops
  • Drop-in compatibility with aluminum variants
Applications
  • High-performance compute racks
  • AI/HPC clusters
  • Data centers
  • Industrial power modules
  • Automotive high-power electronics
Specifications
Part Number Lifecycle
Status
Plate Dimension (mm) Weight (gr) Material Flow Rate
LPM(GPM) 1.0 (0.26)
Flow Rate
LPM(GPM) 2.0 (0.52)
Flow Rate
LPM(GPM) 3.0 (0.79)
Flow Rate
LPM(GPM) 4.0 (1.05)
Length Width Height R
(°C/W)
dP
kPA (psi)
R
(°C/W)
dP
kPA (psi)
R
(°C/W)
dP
kPA (psi)
R
(°C/W)
dP
kPA (psi)
ATS-AIC-3778 ACTIVE 118.0 92.4 31.0 188 Cu 0.023 2.41 (0.35) 0.014 8.62 (1.25) 0.01 18.96 (2.75) 0.008 31.58 (4.58)
Thermal Performance
Schematic Image Thermal Resistance
Flow Rate
LPM(GPM)
R
(°C/W)
dP
kPA (psi)

*Image above is for illustration purpose only.
1.0 (0.26) 0.023 2.41 (0.35)
2.0 (0.52) 0.014 8.62 (1.25)
3.0 (0.79) 0.01 18.96 (2.75)
4.0 (1.05) 0.008 31.58 (4.58)
5.0 (1.32) 0.007 49.99(7.25)
6.0 (1.58) 0.006 71.71(10.4)
ATS-AIC-3778    (Data Sheet)
download data sheet
RoHS & REACH Certificate download data sheet
Complete Your Liquid Loop with ATS

ATS has the products needed to design a complete liquid cooling loop : iCDMs (Industrial Cooling Distribution Modules), Tubed and High Performance Cold Plates to transfer and remove the heat from the source; Heat Exchangers to transfer heat from the liquid to the air with or without a fan; Chillers to circulate and condition the fluid in the system, Compact Refrigeration Modules for very high capacity cooling. In addition , ATS offers Flow Meters to measure the volumetric flow rate of the fluid in the system and Leak Detectors to notify users of any leaks in the system.