ATS Products

RoHS & REACH Certificate Check Distribution Stock
Frequently Asked Questions ?
  • Cost effective thermal management solution for component cooling where the heat load is low to moderate
  • Compatible with industry accepted coolants
  • The cold plate base the copper tubes press into is made of aluminum 6063
  • Copper tubed cold plates are attached to the base plate with a thin film of high thermal conductivity epoxy for secure tube attachment.
  • Stainless steel tubed cold plates are SS 304/316 and feature tubing secured between two plates
  • Supplied with secure, 3/8“ push-to-connect tube fittings for a tight connection between the cold plate and inlet and outlet tubing. Tube outer diameter is 3/8“ (9.525 mm).
  • Maximum pressure: 200 psi
  • Plastic tubing connecting to our Cold Plate fitting has to be at least 90 durometer Shore A scale
Part Number Plate Dimension (mm) Overall
Length
(mm)
# No
of Tube
Pass
Tube
Material
Flow Rate
0.5 gpm
Flow Rate
1.0 gpm
Flow Rate
1.5 gpm
Flow Rate
2.0 gpm
Data Sheet RoHS & REACH
Length Width Height R
(°C/W)
dP
kPA (psi)
R
(°C/W)
dP
kPA (psi)
R
(°C/W)
dP
kPA (psi)
R
(°C/W)
dP
kPA (psi)
ATS-TCP-2006 914.0 106.0 12.7 990.2 4 Copper 0.0057 1.43 (0.21) 0.0047 4.83 (0.70) 0.0042 9.93 (1.44) 0.004 16.64 (2.41) download data sheet
Thermal Performance
Schematic Image Cold Plate Thermal Resistanc
Flow Rate
(gpm)
R
(°C/W)
dP
kPA (psi)

*Image above is for illustration purpose only.
0.5 0.0057 1.43 (0.21)
1.0 0.0047 4.83 (0.70)
1.5 0.0042 9.93 (1.44)
2.0 0.004 16.64 (2.41)