ATS Products

RoHS & REACH Certificate Check Distribution Stock
Frequently Asked Questions ?
  • Cost effective thermal management solution for component cooling where the heat load is low to moderate
  • Compatible with industry accepted coolants
  • The cold plate base the copper tubes press into is made of aluminum 6063
  • Copper tubed cold plates are attached to the base plate with a thin film of high thermal conductivity epoxy for secure tube attachment.
  • Stainless steel tubed cold plates are SS 304/316 and feature tubing secured between two plates
  • Supplied with secure, 3/8“ push-to-connect tube fittings for a tight connection between the cold plate and inlet and outlet tubing. Tube outer diameter is 3/8“ (9.525 mm).
  • Maximum pressure: 200 psi
  • Plastic tubing connecting to our Cold Plate fitting has to be at least 90 durometer Shore A scale
Part Number Plate Dimension (mm) Overall
Length
(mm)
# No
of Tube
Pass
Tube
Material
Flow Rate
0.5 gpm
Flow Rate
1.0 gpm
Flow Rate
1.5 gpm
Flow Rate
2.0 gpm
Data Sheet RoHS & REACH
Length Width Height R
(°C/W)
dP
kPA (psi)
R
(°C/W)
dP
kPA (psi)
R
(°C/W)
dP
kPA (psi)
R
(°C/W)
dP
kPA (psi)
ATS-TCP-2021 304.8 177.8 19.0 383.15 4 304SS OR 316SS SEAMLESS 0.018 0.13 (0.02) 0.014 0.43 (0.06) 0.013 0.89 (0.13) 0.012 1.5 (0.22) download data sheet
Thermal Performance
Schematic Image Cold Plate Thermal Resistanc
Flow Rate
(gpm)
R
(°C/W)
dP
kPA (psi)

*Image above is for illustration purpose only.
0.5 0.018 0.13 (0.02)
1.0 0.014 0.43 (0.06)
1.5 0.013 0.89 (0.13)
2.0 0.012 1.5 (0.22)