CDU-X3MW

Liquid Cooling iCDM CDU-X3MW
*Image above is for illustration purpose only..
CDU-X3MW
Floor-mount Cooling Distribution Module

The ATS CDU-X3MW is a floor-mount, high-capacity Coolant Distribution Unit engineered to deliver continous 3.15 MW of precise single-phase cooling for today’s most demanding data center and industrial systems.

Combining robust mechanical design, intelligent PLC control, and reliable dual–redundant operation, the CDU-X3MW provides efficient, monitored, and service–ready thermal management for AI clusters, HPC servers, and high–power electronics.

Features & Benefits
  • Massive Cooling Power —Provides up to 3.15 MW of single–phase liquid cooling for high–density data center and industrial applications.
  • Rugged Construction —Heavy–duty structural–steel chassis with powder–coat finish ensures long–term durability and corrosion resistance.
  • Advanced Thermal Control —Motorized valves and liquid–to–liquid heat exchanger deliver intelligent and precise temperature and flow regulation.
  • High Flow Capacity —Achieves 1,600 LPM with a 48 psi pump head for stable performance under demanding thermal loads.
  
  • Intelligent PLC System —Integrated PLC and HMI touchscreen provide real–time monitoring, automated control, and Ethernet remote access.
  • Built–In Redundancy —Dual pumps, PLC, and power supplies maintain uninterrupted cooling during maintenance or fault conditions.
  • Comprehensive Safety —Includes over–temperature, over–pressure, low–flow, leak, and emergency–shutdown protection.
  • Service–Friendly Design —Replaceable strainer filter and variable–speed pump control allow efficient, on–the–fly maintenance and optimized power use.
Applications
  • AI and HPC compute racks
  • Immersion-cooled server banks
  • High-density data centers
  • Industrial power electronics cooling
  • Mission-critical test systems and energy storage modules
 
Specifications
L=Length; W=Width; D=Diameter;WT=Weight(kg); MCC=Maximum Cooling Capacity; CFR=Coolant Flow Rate; RV=Reservoir Volume ; FC=Fluid Connections; PIC=Power Input Current; OE=Operating Environment; OHR=Operating Humidity Range;
Part NumberDIMENSIONS (mm)WTCCCFRRVFCPICOEOHR
LWD
CDU-X3MW 2200 1200 1200 1,240 Kg 3,150 kW
(3.15 MW)
1,600 LPM
(422.7 GPM)
80 L
(21.1 Gal)
2.5" sanitary flanges
(4 ports)
35 A 4–40°C
(39.2–104°F)
0–90% RH
Complete Your Liquid Loop with ATS

ATS has the products needed to design a complete liquid cooling loop : iCDMs (Industrial Cooling Distribution Modules), Tubed and High Performance Cold Plates to transfer and remove the heat from the source; Heat Exchangers to transfer heat from the liquid to the air with or without a fan; Chillers to circulate and condition the fluid in the system, Compact Refrigeration Modules for very high capacity cooling. In addition , ATS offers Flow Meters to measure the volumetric flow rate of the fluid in the system and Leak Detectors to notify users of any leaks in the system.