Tag Archives: liquid cooling

New Consulting Project Subscription Plan

ATS has released a Consulting Project Subscription Plan (CPSP) for engineering services. From our corporate headquarters in Norwood, Massachusetts,we offers comprehensive thermal management analysis and design services for the telecommunications, medical, military, defense, aerospace, automotive, and embedded computing industries. The new plan allows ATS engineers to become an extension of your team for a pre-determined amount of hours, providing expert thermal and mechanical engineering consultation, design, simulation, testing and validation.

ATS Design Services

Services include Design, Simulation, Testing, Analysis & Prototyping

The CPSP includes the use of ATS thermal lab facilities and covers all projects approved by an authorized representative of subscribed customers. ATS thermal management analysis and design services encompass both experimental and computational simulations using proprietary tools and computational fluid dynamics software packages such as FLOTHERM and CFdesign.

Thermal Testing & Analysis

Thermal Testing & Analysis

The new subscription plan gives customers priority access to ATS engineering and manufacturing resources for all chip, board, enclosure, and system related projects. ATS studies the full packaging domain, including components, circuit boards (PCBs), shelves, chassis, and system packaging.

Consulting capabilities include:

– heat sink, board and fan characterization

– heat sink design and optimization

– PCB & fan tray design and optimization

– liquid cooling design

– prototyping of heat sinks and complete cooling systems

– wind tunnel testing of components, PCBs, chassis and enclosures

ATS offers rapid prototyping of machined parts and cooling systems from its US facilities. Sheet metal fabrication and cut heat sink prototypes are quickly provided from international partners.

Liquid Crystal Thermography

Liquid Crystal Thermography

ATS believes that customers who wish to remain competitive should consider a design-to-suit opportunity solution first. Contrary to common perception, this proves to be less expensive to the customer in the long run, because of the ensuing gain in product efficiency and compatibility. Working side-by-side with customers worldwide, ATS engineers provide tailored solutions to thermal and mechanical packaging challenges on real projects with real schedules.

To learn more about the consulting project subscription plan, call 781-769-2800, email ats-hq@qats.com, or visit www.qats.com.

The New iFLOW-200 Tests and Measures the Thermal and Hydraulic Performance of Cold Plates

Advanced Thermal Solutions, Inc. (ATS) has released a new thermal test instrument, the iFLOW-200, which assesses the thermal and hydraulic characteristics of cold plates in electronics cooling. It can be used to simulate a wide range of conditions to optimize a cold plate’s performance before it is commercialized or prior to its use in an actual application.

 

The iFLOW-200 measures coolant temperatures from 0-70°C with the high accuracy of ± 1°C. Differential pressure of the coolant in the cold plate is measured up to 103,000 Pa (15 psi), with the precise accuracy of ± 1%. Distilled water is used as the reference coolant. For test comparisons, the systems coolingVIEW software can also calculate thermal resistance and pressure drop as a function of flow rate for selected liquids.

 

The instrument system includes a pair of K-type thermocouples for measuring temperature changes on the cold plate surface. Temperatures are monitored on the coolingVIEW interface.

 

The iFLOW-200 system features easy set up and operation to save time when evaluating different cold plate models. Designed for accuracy and convenience, the iFLOW-200 simply requires setting the starting and ending coolant flow rates, and choosing the dwell time, pumping power and other parameters. These are easily done on any PC using the systemd user-friendly application program.

The iFLOW-200 system features separate controller and hydraulics enclosures with USB connections. The hydraulic package includes a fluid level indicator, coolant inlets and outlets from/to the cold plate under test, ports for surface temperature thermocouples, and a fluid cooling system for its internal heat exchanger. The iFLOW-200 is also ideal for testing alternative liquids.

 

More information about the iFLOW-200 Cold Plate Characterization System can be found at http://www.qats.com/Products/Temperature-and-Velocity-Measurement/Instruments/iFLOW-200

How to Calculate Heat Loads for Liquid Cooling Systems

A series of calculations can be used to find the thermal loads in common liquid cooling systems. Calculations of this nature are needed to predict the performance of liquid cooling systems, which are effective but complex thermal management solutions. Several equations must be calculated to fully understand the behavior of a liquid cooled system, and ATS is providing these to engineers via personal instruction and in a paper available free from the company’s website, Qats.com.

IIn the paper, which appears in the company’s e-magazine, ATS considers a liquid cooling system as a closed loop system with three major components: cold plate, heat exchanger and pump. The cold plate is typically made from aluminum or copper, and is attached to the device being cooled. The plate usually has internal fins which transfer heat to the coolant flowing through them. This fluid moves from the cold plate to a heat exchanger where its heat is transferred to the ambient air via forced convection. The final part of the cooling loop is the pump, which drives the fluid through the loop.

A series of equations is provided to predict the final temperature of the device being cooled. The first of these equates the surface temperature of this device with the product of the power dissipated by the device times the thermal resistance of the cold plate (and its thermal interface material), added to the temperature of the water entering the cold plate.

The sequence of calculations factors in specifications from the cold plate, heat exchanger and pump. The result is a solution for the device temperature as a function of cold plate resistance. In the example cited by ATS, a cold plate thermal resistance of less than 18 degrees C/W is required to cool an Intel Xeon 5492 processor in a 25C temperature environment.

Liquid cooling is an important and expanding practice in the electronics industry. It is important to understand the impact on performance of all three major parts of liquid cooling loops (cold plate, heat exchanger and pump) to ensure an acceptable level of performance at the lowest cost.

Instructions for calculating load for liquid cooling systems are available on Qats.com in the pages of Qpedia, the thermal management emagazine from ATS. More information is also available by calling 1-781-949-2522.

How to Mix Water and Air for Electronics Cooling (part 2 of 2)

In part 1 of our 2 part series on Hybrid Liquid/Air Cooling Systems and how you can use them to cool some of your toughest thermal challenges, we covered the air portion of our system, here in part 2 we’ll consider the liquid portion and how to integrate them.

Unless one is using a natural body of water for coolant, or operating in space, at the end of every cooling solution there is a liquid to air heat exchanger, when the generated heat is transferred.

Typical Liquid Cooling SystemFigure 2. Typical Liquid Cooling System

As shown in Figure 2, a conventional liquid cooling system consists of a cold plate, external plumbing, and a heat exchanger. The advantage of this type of system is to increase flexibility in packaging by allowing remote placement of the heat exchanger. Remote mounting does introduce disadvantages, as the external plumbing increases pressure drop throughout the system, which increases the required pumping power. The piping itself is a potential source of leakage at the plumbed junctions, as is the permeability of the piping system.

To appreciate the importance of spreading resistance, lets assume a high heat flux component generates 500 W/cm2 in a 10 x 10 mm package. The size of the copper heat sink used is 80 x 80 mm, with a base thickness of 5 mm. The spreading resistance alone for this case is 0.140C/W. Even if the thermal resistance of the heat sink is 0 (thermodynamically impossible), the temperature rise of the component above ambient is 700C. Considering an ambient of 500C, the above proposed heat sink will not cool the device adequately to prevent it from failure. The above example shows how important the spreading resistance is, especially in high heat flux applications.

There are many methods for reducing the thermal resistance. Among these methods are:

Use of a high conductivity material as the base plate of the heat sink to reduce thermal resistance. These materials include aluminum (k = 180 W/mK), copper (k = 380 W/mK), and CVD diamond (k = 2000 W/mK).
Using passive, high conductivity devices, like heat pipes, thermosyphons, or vapor chambers
Use of thermoelectric devices whose heat spreader structures consist simply of an electrically conductive heat sink with an applied external electric potential.

This induces a Thomson Effect, and provides heat transfer through the device. Of the above, the vapor chamber has been the most desirable method. Basically, a vapor chamber works like a heat pipe. The heat transfer to the base vaporizes the liquid and reaches the cold section of the chamber. The vapor condenses and returns back to the base with the help of the wick structure. But, even though the spreading resistance of a vapor chamber is theoretically appealing, it has been found that, under certain conditions, a solid copper spreader can have lower thermal spreading resistance [2,3,4].

comparison of solid copper heat sink and vapor chamberFigure 3. Comparison of a Solid Copper Heat Sink and a Vapor Chamber

In order to alleviate spreading resistance issues, Advanced Thermal Solutions, Inc. (ATS) has developed a new technology, the Forced Thermal Spreader, or FTS [5]. A schematic picture of the FTS design is shown in Figure 4.

Structure of Advanced Thermal Solutions Thermal SpreadersFigure 4. Structure of Advanced Thermal Solutions’ Forced Thermal Spreader

The FTS design is a combination of mini- and microchannels.

The heat transfer coefficient in the micro-channels is about 500,000 W/m20C. This high heat transfer coefficient creates a very small resistance between the heat source and the incoming liquid. The heat is then transferred to the bottom of the heat sink with the minifins attached to the top plate. Heat then transfers from the top plate to the ambient through the heat sink. The experimental test set up is shown in figure 5.

An experiment with an FTS was performed using an HFC-100 test equipment developed by ATS. The HFC-100 is a computerized data acquisition system capable of controlling up to 1KW of heat generated on a 1 cm2 simulated chip. This instrument is capable of ramping the heat with specified dwell times. The size of the FTS was 100 x 120 mm. Table 1 shows the experimental data from tests performed at power levels of 100, 200, and 300 W/cm2. The results show that the data is independent of the power. The experiment was conducted several times at each power level to ensure data repeatability.

Forced Thermal Spreader Test Set UpFigure 5. Forced Thermal Spreader Test Setup

Experimental Data  for the Thermal Resistance of the FTSTable 1b: Experimental Data for the Thermal Resistance of the Forced Thermal Spreader

The thermal resistance from the FTS is around 0.1370C/W on average. The water flow rate is set as 1.0~1.2 L/min, and it was observed that increasing the flow rate beyond 0.3 L/min had no noticeable change in temperature. One very noticeable phenomenon is the interfacial resistance. Because the heat source is small, 1 cm2, this resistance value is significant even under best contact conditions. It is expected that this number would be much higher in a real device application. For proof, a second experiment was carried out. In this experiment the heat source was made part of the FTS, which eliminated the spreading resistance.

Table 2 shows the data for this case. The thermal resistance of the FTS is about 0.14 to 0.15oC/W.

 

Experimental Data for the Thermal Resistance of the FTS, With No Interfacial ResistanceTable 2. Experimental Data for the Thermal Resistance of the FTS, With No Interfacial Resistance

The importance of the above numbers shows itself when calculating the spreading resistance. For a 100mm x 120mm base size copper heat sink, and a 10mm x 10mm heat source, the spreading resistance is about 0.12 degree C/W.  To achieve the total resistance of 0.14 degree C/W with a copper heat sink, we need a heat sink resistance of 0.02 degree C/W, which is not feasible using just air. To show this, we can look at the thermal resistance of a heat sink:

thermal resistance of a heat sink

Where Cp is the fluid heat capacitance, h is heat transfer coefficient, and is the mass flow rate. Assuming a heat transfer coefficient of infinity (thermodynamically impossible):

coefficient of infinity

To reach a resistance of 0.02oC/W, a velocity of 25 m/sec is required for a heat sink that is 100 mm wide and 20 mm high. In a typical systems environment, the h value is about 100-200 W/m2oC for very high speed flows. Assuming this heat sink has 65 fins at 1 mm spacing, the convective resistance will be around 0.02oC/W, but with an enormous amount of pressure drop of about 20 kpa (80H2O). This is clearly an impractical situation.

The data presented in this article shows that an effective hybrid system (liquid-assisted air cooling) has enormous capability for high heat flux applications. However the reader should not forget that the interfacial thermal resistance will always exist unless the interface is eliminated by integrating the cooling and the package systems. Equally important is the reliability of the cooling loops, as well as active control of the device functionality should the cooling system fail.

Got a question on part 1 or 2? Contact us and lets see how ATS’ thermal engineers can make your next project a success! Email us at ats-hq@qats.com , call us at 781-769-2800 or visit our Design Services
References:

1. Soul, C., The Benefits of Liquid Cooling over Air Cooling for Power Electronics, www.icepak.com/prod/icepak/solutions/articles/iceart19.htm
2. Sauciu, I., Chrysler, G., Mahajan, R., Spreading in the Heat Sink Base: Phase Change Systems or Solid Metals?, IEEE Transactionson Components and Packaging Technologies, Vol 23, No.4., 2002.
3. Jeung, S., Quantitative Thermal Performance Evaluation of a Cost-effective Vapor Chamber Heat Sink Containing a Metaletched Microwick Structure for Advanced Microprocessor Cooling, Sensors and Actuators, A: Physical Volume 121, Issue 2, 2005.
4. Wei, J., Cha, A., Copeland, D., Measurement of Vapor Chamber Performance, IEEE SEMI-THERM Symposium, 2003.
5. Xiong, D., Azar, K., Tavossoli, B., Experimental Study on a Hybrid Liquid/Air Cooling System, IEEE, Semiconductor Thermal Measurement
and Management Symposium 2006.

 

How to Mix Water and Air for Electronics Cooling (part 1 of 2)

As electronics become faster and more powerful, thermal management solutions must evolve to deal with the increasing heat loads. Simply increasing the size of a heat sink, or adding a fan, was once enough to provide the required increased performance. But, while air cooling remains the dominant method of thermal management in the electronics industry, there are applications where traditional air cooling is not sufficient. These are bound to increase in frequency in the near future. This week we have a two part series on Hybrid Liquid/Air Cooling Systems and how you can use them to cool some of your toughest thermal challenges.

Today, liquid cooling is being used in a steadily increasing number of thermal applications. Desktops, servers, and even laptops are all potential products for such cooling methods. The attractiveness of liquid is its density and specific heat over air (Table 1). However, these material properties can be misleading if compared side by side.

Physical Properties of Air and Water
Table 1: Physical Properties of Air and Water[1]

In electronics, there is no basis for comparison between air and liquid for cooling. The term liquid cooling is itself misleading, as air is the final coolant in nearly all applications. The role of the liquid is not as a coolant, but as an active thermal transport vehicle. The main benefit from using liquid is the reduced thermal resistance from the heat source to the air cooled system peripheries. This is due to forced convection replacing pure conduction as the heat transport method, where the heat is delivered to the convective surfaces.

In general, all electronics cooling systems can be divided into three important components as shown in Figure 1:

  • Interface
  • Heat spreading
  • Ambient heat exchanger

Diagram of an Electronics Cooling SystemFigure 1: Typical Electronics Cooling System used in Thermal Management

The Interface refers to the junction between the component and heat sink or cold-plate. This resistance is typically minimized with a high performance grease or phase-change material, and is the same in both liquid and air cooling systems.

The spreading resistance in a thermal solution can be described as the transport of heat from the component to the cooling surfaces that are in contact with the ambient air. This is the only part of a cooling system that greatly differs from air to liquid cooling. With a typical air cooled heat sink, the thermal spreading is done at the base of the heat sink through pure conduction. When using liquid, the spreading is done by the movement of the liquid in a loop from the cold-plate to heat exchanger by mass transport, i.e. coolant.

The final part of an electronics cooling system is the ambient heat exchanger. For air cooling, this part is the heat sink fins, and for liquid cooling is the radiator fins. Both systems work in the same way, by using extended surfaces (fins) to transfer heat into the ambient air through convection.

In part 2 we’ll cover the liquid part of our article and more about integrating for a best in class solution!

Got a question on part 2 already or maybe part 1 from today? Contact us and lets see how ATS thermal engineers can make your next project a success! Email us at ats-hq@qats.com , call us at 781-769-2800 or visit our Design Services

——————————-
References:

1. Soul, C., The Benefits of Liquid Cooling over Air Cooling for Power Electronics, www.icepak.com/prod/icepak/solutions/articles/iceart19.htm
2. Sauciu, I., Chrysler, G., Mahajan, R., Spreading in the Heat Sink Base: Phase Change Systems or Solid Metals?, IEEE Transactionson Components and Packaging Technologies, Vol 23, No.4., 2002.
3. Jeung, S., Quantitative Thermal Performance Evaluation of a Cost-effective Vapor Chamber Heat Sink Containing a Metaletched Microwick Structure for Advanced Microprocessor Cooling, Sensors and Actuators, A: Physical Volume 121, Issue 2, 2005.
4. Wei, J., Cha, A., Copeland, D., Measurement of Vapor Chamber Performance, IEEE SEMI-THERM Symposium, 2003.
5. Xiong, D., Azar, K., Tavossoli, B., Experimental Study on a Hybrid Liquid/Air Cooling System, IEEE, Semiconductor Thermal Measurement
and Management Symposium 2006.