{"id":9998,"date":"2019-04-11T09:12:27","date_gmt":"2019-04-11T13:12:27","guid":{"rendered":"http:\/\/www.qats.com\/cms\/?p=9998"},"modified":"2019-04-11T09:56:33","modified_gmt":"2019-04-11T13:56:33","slug":"application-of-air-jet-impingement-for-cooling-a-1u-system","status":"publish","type":"post","link":"https:\/\/www.qats.com\/cms\/2019\/04\/11\/application-of-air-jet-impingement-for-cooling-a-1u-system\/","title":{"rendered":"Application of Air Jet Impingement for Cooling a 1U System"},"content":{"rendered":"\n<p class=\"wp-block-paragraph\">As their speeds increase, the heat dissipation from high performance processors requires more innovative cooling techniques for heat removal. One such technique, jet impingement, provides one of the highest heat transfer coefficients among cooling methods. This property of jet impingement has been used by Advanced Thermal Solutions, Inc. (ATS) in a 1-U server application. Jet impingement has also been applied to ATCA chassis.<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img loading=\"lazy\" decoding=\"async\" width=\"1024\" height=\"623\" src=\"http:\/\/www.qats.com\/cms\/wp-content\/uploads\/Server-1024x623.jpg\" alt=\"Air Jet Impingement\" class=\"wp-image-10005\" srcset=\"https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Server-1024x623.jpg 1024w, https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Server-300x183.jpg 300w, https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Server-800x487.jpg 800w, https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Server.jpg 1920w\" sizes=\"auto, (max-width: 1024px) 100vw, 1024px\" \/><figcaption>Cooling high-powered 1U servers requires new thermal management techniques, including advanced air jet impingement. (Wikimedia Commons)<br><\/figcaption><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">A Ujet-1000&#x2122; 1-U chassis made by ATS was assessed in the company\u2019s thermal test lab. Four identical heat sinks were tested under conventional parallel flow and ATS\u2019 proprietary Therm-Jett<sup>&#x2122; <\/sup>impingement flow. The results showed a 20-40 percent improvement in the thermal performance of the heat sinks. <\/p>\n\n\n\n<p class=\"wp-block-paragraph\">The\nUjet-1000&#x2122; is a 1 to 2 KW 1-U chassis system (depending on component case and\nambient temperature) designed for the most demanding, telecom and server\napplications. Lab tests demonstrated that four heat sinks on four simulated\nchips located on a PCB achieved 0.16 to 0.18<sup>o<\/sup>C\/W thermal resistance.\nThe power dissipation of each simulated component was maintained at 200 W. On\nthe other hand, the thermal resistance of the same heat sinks with parallel\nflow, using the same fans, was almost 20 to 40% worse. <\/p>\n\n\n\n<p class=\"wp-block-paragraph\">The new ATS Therm-Jett<sup>&#x2122;<\/sup> technology uses a specially made duct with an impingement plate beneath it to create jet impingement on top of the components and heat sinks. The tremendous increase in heat transfer coefficient leads to significant reduction of thermal resistance compared to the other conventional 1-U systems. A Therm-Jett<sup>&#x2122;<\/sup> system can be built for any specific configuration. The impingement duct is less than 5 mm thick and is located in the chassis on top of the motherboard. In addition to high heat transfer coefficient, fresh air is distributed between all heat sinks at inlet temperature. <\/p>\n\n\n\n<p class=\"wp-block-paragraph\">In\ncontrast, in conventional cooling systems, the upstream heat sinks and\ncomponents receive air at inlet temperatures which are cold and gradually warm\nup as the air moves downstream. The increase of air temperature effectively\nreduces the cooling effect of the air downstream. <\/p>\n\n\n\n<p class=\"wp-block-paragraph\">The other advantage of Therm-Jett&#x2122; is that there is no need to make a special duct for each heat sink, thus freeing the motherboard for other components. Even by adding ducts, other components such as memory cards, resistors and capacitors located upstream of the heat sinks on the PWB would deprive the heat sink of the flow at its most critical point, which is close to the base.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Figure\n1 shows a CAD drawing of the real system under test. The cooling is provided by\neight 40 mm high capacity double fans located in the midsection of the 1-U\nchassis. The power to the heat sinks was provided by four heaters attached below\nand dissipating 200 W each. The heat dissipation of the power supply was simulated\nby attaching a rectangular heater strip under the power supply which dissipates\nabout 100 W. A \u201cU\u201d shape frame made of aluminum was located under the hard\ndrives. The power of four hard drives was simulated by placing a rectangular\nheater under the \u201cU\u201d shape frame which dissipates about 80 W. <\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Four\nthermocouples were placed in holes at the center of the base of the heat sink\ndownstream. The holes were filled with thermal grease to minimize the interfacial\nresistance. Three thermocouples were attached to the aluminum \u201cU\u201d frame, and\ntheir average temperature was recorded as an approximate temperature of a real\nhard drive. One thermocouple was also attached to the base of the power supply\nto measure its approximate temperature. All temperature measurements were taken\nusing J type thermocouples.<\/p>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"612\" height=\"397\" src=\"http:\/\/www.qats.com\/cms\/wp-content\/uploads\/Fig-1-19.jpg\" alt=\"\" class=\"wp-image-9999\" srcset=\"https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Fig-1-19.jpg 612w, https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Fig-1-19-300x195.jpg 300w\" sizes=\"auto, (max-width: 612px) 100vw, 612px\" \/><figcaption>Figure 1. Schematic of the Ujet-1000TM and the Therm-JETT&#x2122; cooling duct. (Advanced Thermal Solutions, Inc.)<\/figcaption><\/figure><\/div>\n\n\n\n<p class=\"wp-block-paragraph\">Figure 2 shows the exploded view of the Ujet-1000&#x2122; chassis. <\/p>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"622\" height=\"540\" src=\"http:\/\/www.qats.com\/cms\/wp-content\/uploads\/Fig-2-19.jpg\" alt=\"\" class=\"wp-image-10000\" srcset=\"https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Fig-2-19.jpg 622w, https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Fig-2-19-300x260.jpg 300w\" sizes=\"auto, (max-width: 622px) 100vw, 622px\" \/><figcaption>Figure 2. Exploded view of the Ujet-1000TM and the Therm-JETT&#x2122; cooling duct. (ATS)<\/figcaption><\/figure><\/div>\n\n\n\n<p class=\"wp-block-paragraph\">Figure 3 shows a conventional cooling system for a 1-U system. In this system, the air flow from the fans is parallel to the heat sinks. <\/p>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"634\" height=\"460\" src=\"http:\/\/www.qats.com\/cms\/wp-content\/uploads\/Fig-3-20.jpg\" alt=\"\" class=\"wp-image-10001\" srcset=\"https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Fig-3-20.jpg 634w, https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Fig-3-20-300x218.jpg 300w\" sizes=\"auto, (max-width: 634px) 100vw, 634px\" \/><figcaption>Figure 3. Conventional Cooling System in a 1-U Application. (ATS)<\/figcaption><\/figure><\/div>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Results<\/strong><\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Figure 4 shows the schematic set up of the conventional cooling system. In this configuration, eight (8) blowers move the air in parallel to the heat sink fins.<\/p>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"562\" height=\"381\" src=\"http:\/\/www.qats.com\/cms\/wp-content\/uploads\/Fig-4-20.jpg\" alt=\"\" class=\"wp-image-10002\" srcset=\"https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Fig-4-20.jpg 562w, https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Fig-4-20-300x203.jpg 300w\" sizes=\"auto, (max-width: 562px) 100vw, 562px\" \/><figcaption>Figure 4. Configuration of conventional layout in a 1U system for temperature measurement. (ATS)<\/figcaption><\/figure><\/div>\n\n\n\n<p class=\"wp-block-paragraph\">Figure 5 shows the implementation of an ATS Therm-Jet, which provides jet impingement on the same four heat sinks, and the location of impingement holes with respect to the heat sinks.<\/p>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"560\" height=\"374\" src=\"http:\/\/www.qats.com\/cms\/wp-content\/uploads\/Fig-5-8.jpg\" alt=\"\" class=\"wp-image-10003\" srcset=\"https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Fig-5-8.jpg 560w, https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Fig-5-8-300x200.jpg 300w\" sizes=\"auto, (max-width: 560px) 100vw, 560px\" \/><figcaption>Figure 5. Configuration of an ATS Therm-JETT&#x2122; application in a 1U system for temperature measurement. (ATS)<\/figcaption><\/figure><\/div>\n\n\n\n<p class=\"wp-block-paragraph\">Tables 1 and 2 show the experimental values obtained within a 1-U chassis made by ATS. The two sets of tests were done for both 12 and 6 volts to the fans. The thermal resistance data of all four heat sinks, hard drives and the power supply were obtained for both conventional cooling and jet impingement cases. The acoustic noise for each case was also recorded for comparison. <\/p>\n\n\n\n<p class=\"wp-block-paragraph\">The data shows an improvement of thermal resistance of 22% to 42% for the heat sinks from jet impingement as compared to conventional cooling. The power supply shows a 10% improvement in the thermal resistance. <\/p>\n\n\n\n<p class=\"wp-block-paragraph\">The\nhard drive, though, shows a 20% degradation. This is due to the fact that, with\njet impingement, the pressure drop on the fans increases, consequently\ndecreasing the flow through the system. However in an actual system the\npercentage will be smaller. That\u2019s because the heat generated will be more\nvolumetric compared to the current setup where heat is generated on the surface\nof the \u201cU\u201d shape aluminum piece located at the bottom of hard drives. <\/p>\n\n\n\n<p class=\"wp-block-paragraph\">In that case, the decrease of flow through the system will have less impact. Additionally, the increase in hard drive temperature is less than 2\u00b0C in this experiment, which is generally not large enough to be a concern.<\/p>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"653\" height=\"225\" src=\"http:\/\/www.qats.com\/cms\/wp-content\/uploads\/Table-1-7.jpg\" alt=\"\" class=\"wp-image-10006\" srcset=\"https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Table-1-7.jpg 653w, https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Table-1-7-300x103.jpg 300w\" sizes=\"auto, (max-width: 653px) 100vw, 653px\" \/><figcaption>Table 1. Experimental test results comparing conventional and Therm-JETT&#x2122; results with 12 volts to the fans.<\/figcaption><\/figure><\/div>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"676\" height=\"241\" src=\"http:\/\/www.qats.com\/cms\/wp-content\/uploads\/Table-2-2.jpg\" alt=\"\" class=\"wp-image-10007\" srcset=\"https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Table-2-2.jpg 676w, https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Table-2-2-300x107.jpg 300w\" sizes=\"auto, (max-width: 676px) 100vw, 676px\" \/><figcaption>Table 2. Experimental test results comparing conventional and Therm-JETT&#x2122; results with six volts to the fans.<\/figcaption><\/figure><\/div>\n\n\n\n<p class=\"wp-block-paragraph\">The\nquestion might be raised as to whether the performance of the heat sinks could\nbe improved if we removed the impingement duct, increased the heat sink height\nby the height of impingement duct and ducted the flow. <\/p>\n\n\n\n<p class=\"wp-block-paragraph\">We\nanalyzed this situation and found that the improvement would be at most 5%, if\nwe assume that the heat sink is ducted and the pressure drop is the same in\nboth short and tall versions. To study this problem in detail one must consider\nthe fan curves instead of using a fixed volumetric flow rate. Interested\nreaders will find an article in a previous issue of the ATS Qpedia Thermal eMagazine\n[1] with more information about this topic. <\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Table 3 shows the temperatures of the four heat sinks, the hard drive and the power supply. As we mentioned earlier, the heat sinks were mounted on 200 W devices, the power supply was dissipating 100 W and the hard drives were dissipating 80 W. The results are shown for jet impingement and conventional parallel air flow over 23.5 mm tall heat sinks, and ducted flow over heat sinks with 28.5 mm tall heat sinks. It can be seen that heat sink temperatures are significantly lower for jet impingement even compared with a taller heat sink with ducted flow.<\/p>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"727\" height=\"483\" src=\"http:\/\/www.qats.com\/cms\/wp-content\/uploads\/Table-3-1.jpg\" alt=\"\" class=\"wp-image-10008\" srcset=\"https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Table-3-1.jpg 727w, https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Table-3-1-300x199.jpg 300w\" sizes=\"auto, (max-width: 727px) 100vw, 727px\" \/><figcaption>Table 3. Comparison of temperatures for jet impingement and parallel flow with 23.5 mm heat sinks and ducted flow with 28.5 mm tall heat sinks.<\/figcaption><\/figure><\/div>\n\n\n\n<p class=\"wp-block-paragraph\">Table 4 shows the improvement in temperature of the four processors between the jet impingement and the two cases of 23.5 mm heat sink and the ducted 28.5 mm heat sinks. By comparing the results for 6 and 12 volts to the fans, it can be seen that at lower voltage the jet impingement temperature difference is even more than with higher voltage to the fans. This implies low pressure drop fans can significantly benefit from the application of jet impingement.<\/p>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"651\" height=\"471\" src=\"http:\/\/www.qats.com\/cms\/wp-content\/uploads\/Table-4-1.jpg\" alt=\"\" class=\"wp-image-10009\" srcset=\"https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Table-4-1.jpg 651w, https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Table-4-1-300x217.jpg 300w\" sizes=\"auto, (max-width: 651px) 100vw, 651px\" \/><figcaption>Table 4. Comparison of temperature improvement for jet impingement and parallel flow with 23.5 mm heat sinks and ducted flow for 28.5 mm tall heat sinks.<\/figcaption><\/figure><\/div>\n\n\n\n<p class=\"wp-block-paragraph\">Figure\n6 is a graphical representation of Table 4. The figure shows the significant\ntemperature increases in the case of parallel flow and ducted flow for the heat\nsinks compared to jet impingement technology. Components (heat sinks) 2 and 3\nare hotter than components 1 and 2 because they are downstream and the approach\nair temperature is higher for a ducted flow. In the jet impingement mode, the\nimpingement flow is at upstream temperature and therefore much cooler than the\nair received in ducted flow. <\/p>\n\n\n\n<p class=\"wp-block-paragraph\">In impingement mode, there is another flow coming axially toward the components, called cross flow. It is the interaction of cross flow and impingement that causes the cooling of the component (heat sink).<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img loading=\"lazy\" decoding=\"async\" width=\"614\" height=\"402\" src=\"http:\/\/www.qats.com\/cms\/wp-content\/uploads\/Fig-6-10.jpg\" alt=\"\" class=\"wp-image-10004\" srcset=\"https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Fig-6-10.jpg 614w, https:\/\/www.qats.com\/cms\/wp-content\/uploads\/Fig-6-10-300x196.jpg 300w\" sizes=\"auto, (max-width: 614px) 100vw, 614px\" \/><figcaption>Figure 6. Heat sink temperature increase of parallel and ducted flow compared to jet impingement cooling. (ATS)<\/figcaption><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">It\nshould be noted that the above experiment was done for a heat source that is\nthe same size as the heat sink base; hence, the spreading resistance is zero\nbecause it is almost independent of the heat transfer coefficient. The\nspreading resistance can be added to the above numbers for other sizes of heat\nsources.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">The\nsame concept of jet impingement has been applied to simulated components in ATCA\nchassis. The results will be published in subsequent Qpedia articles. The data\nimprovement is promising. Even though conventional air-cooling technology is\nfast approaching its thermodynamic limit, there are still numerous potentials for\nair cooling which will enable this technology to be used in the years to come.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Reference<\/strong><\/p>\n\n\n\n<p class=\"wp-block-paragraph\">1. &nbsp;&#8220;Heat Sink Thermal Resistance as a Function of Height-Ducted Flow with Fan Curve,&#8221; Qpedia Thermal eMagazine, Advanced Thermal Solutions, Inc., January 2009.<\/p>\n\n\n\n<hr class=\"wp-block-separator\"\/>\n\n\n\n<p class=\"wp-block-paragraph\"><em>For more information about Advanced Thermal Solutions, Inc. (ATS) thermal management consulting and design services, visit <\/em><a href=\"https:\/\/www.qats.com\/consulting\"><em>https:\/\/www.qats.com\/consulting<\/em><\/a><em>&nbsp;or contact ATS at 781.769.2800 or&nbsp;<\/em><a href=\"mailto:ats-hq@qats.com\"><em>ats-hq@qats.com<\/em><\/a><em>.\ufeff<\/em><\/p>\n","protected":false},"excerpt":{"rendered":"<p>As their speeds increase, the heat dissipation from high performance processors requires more innovative cooling techniques for heat removal. One such technique, jet impingement, provides one of the highest heat transfer coefficients among cooling methods. This property of jet impingement &hellip; <a href=\"https:\/\/www.qats.com\/cms\/2019\/04\/11\/application-of-air-jet-impingement-for-cooling-a-1u-system\/\">Continue reading <span class=\"meta-nav\">&rarr;<\/span><\/a><\/p>\n","protected":false},"author":1001004,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[925,687],"tags":[914,103,922],"class_list":["post-9998","post","type-post","status-publish","format-standard","hentry","category-jet-impingement","category-servers","tag-data-centers","tag-jet-impingement","tag-servers"],"_links":{"self":[{"href":"https:\/\/www.qats.com\/cms\/wp-json\/wp\/v2\/posts\/9998","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.qats.com\/cms\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.qats.com\/cms\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.qats.com\/cms\/wp-json\/wp\/v2\/users\/1001004"}],"replies":[{"embeddable":true,"href":"https:\/\/www.qats.com\/cms\/wp-json\/wp\/v2\/comments?post=9998"}],"version-history":[{"count":3,"href":"https:\/\/www.qats.com\/cms\/wp-json\/wp\/v2\/posts\/9998\/revisions"}],"predecessor-version":[{"id":10022,"href":"https:\/\/www.qats.com\/cms\/wp-json\/wp\/v2\/posts\/9998\/revisions\/10022"}],"wp:attachment":[{"href":"https:\/\/www.qats.com\/cms\/wp-json\/wp\/v2\/media?parent=9998"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.qats.com\/cms\/wp-json\/wp\/v2\/categories?post=9998"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.qats.com\/cms\/wp-json\/wp\/v2\/tags?post=9998"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}