Utilizing Fans in Thermal Management of Electronics Systems

Fans in Thermal Management

There are different types of fans that are used in thermal management of electronics with tube axial fans being the most common. (Wikimedia Commons)


The ongoing trend in the electronics industry is for increasingly high-powered components to meet the ever-growing demands of consumers. Coupled with greater component-density in smaller packages, thermal management is more and more of a priority to ensure performance and reliability over the life of an electronics system.

As thermal needs have grown, engineers have sought out different cooling methods to supplement convection cooling. While options such as liquid cooling have grown in popularity in recent years, still one of the most common techniques is to add fans to a system.

Through the years, fan designs have improved. Fan blades have been streamlined to produce great flow rate with less noise and fans have become more power-efficient to meet the desires of customers trying to use less resources and save costs.

While much has changed in the presentation of fans, there are many basic concepts that engineers must consider when deciding how to implement fans in a project.

This is part one of a two-part series on how to select the best fan for a project. Part one will cover the types of fans that can be used. Part two, which can be found at https://www.qats.com/cms/2017/03/10/analysis-of-fan-curves-and-fan-laws-in-thermal-management-electronics, will cover fan laws and analyzing fan curves.

COMMON TYPES OF FANS AND BLOWERS

As described by Mike Turner of Comair Rotron in an article for Electronics Cooling Magazine, “All You Need to Know About Fans,” fans are essentially low pressure air pumps that take power from a motor to “output a volumetric flow of air at a given pressure.” He continued, “A propeller converts torque from the motor to increase static pressure across the fan rotor and to increase the kinetic energy of the air particles.”

In a white paper from Advanced Thermal Solutions, Inc. (ATS) entitled, “Performance Difference Between Fans and Blowers and Their Implementation,” it was added that fans are at their core, dynamic pumps. The article added, that in dynamic pumps “the fluid increases momentum while moving through open passages and then converts its high velocity to a pressure increase by exiting into a diffuser section.”

The biggest difference between a fan and a blower is the direction in which the air is delivered. Fans push air in a direction that is parallel to the fan blade axis, while blowers move air perpendicular to the blower axis. Turner noted that fans “can be designed to deliver a high flow rate, but tend to work against low pressure” and blowers move air at a “relatively low flow rate, but against high pressure.”

The three types of fans are centrifugal, propeller, tube axial, and vane axial:

• In centrifugal fans, the air flows into the housing and turns 90 degrees while accelerating due to centrifugal forces before being flowing out of the fan blades and exiting the housing.
• Propeller fans are the simplest form of a fan with only a motor and propellers and no housing.
• Tube axial fans, according to Turner, are similar to a propeller fan but “also has a venture around the propeller to reduce the vortices.”
• Vane axial fans have vanes trailing behind the propeller to straighten the swirling air as it is accelerated.

The most common fans used in electronics cooling are tube axial fans and there are a number of manufacturers creating options for engineers. A quick search of Digi-Key Electronics, offered options such as Sunon, Orion Fans, Sanyo Denki, NMB Technologies, Delta Electronics, Jameco Electronics, and several more.

Fans in Thermal Management

A fan is added to a heat sink on a PCB in order to increase the air flow and heat dissipation from the board component. (Advanced Thermal Solutions, Inc.)

FACTORS TO CONSIDER WHEN PICKING A FAN

When selecting a fan, engineers must consider the specific requirements of the system in which they are working, including factors such as the necessary airflow and the size restrictions of the board or the chassis. These basic factors will allow engineers to search through the many available options to find a fan that fits his or her needs.

In addition, engineers may look towards combining multiple fans in parallel or in a series to increase the flow rate across the components without increasing the size of the package or the diameter of the fan.

Parallel operation means having two or more fans side-by-side. When two fans are working in parallel, then the volume flow rate will be increased, even doubled when the fans are operating at maximum. Turner added. “The best results for parallel fans are achieved in systems with low resistance.”

In a series, the fans are stacked on top of each other and results in increased static pressure. Unlike parallel operations, fans in a series work best in a system with high resistance.

The ATS white paper noted, “In real situations, the fans may interfere with each other. The end results is a lower than expected performance.” Turner warns that in either parallel or series configurations there is a point in the combined performance curve that should be avoided because it creates unstable and unpredictable performance, but analyzing fan performance and fan curves will be covered in more detail in part two of the blog.

Efficiency is a major factor when selecting a fan. As noted in an article from Qpedia Thermal eMagazine, “A large data center contains about 400,000 servers and consumes 250 MW of power. It has been estimated that about 20% of the total power supplied to a high end server is consumed by fans.”

Clearly, finding a fan that can work efficiently with lower power will save a considerable about of resources. The article details several methods for creating efficiency in designing a system that includes fans:

“Fan power consumption is traditionally reduced by controlling the motor speed to produce only the airflow required for adequate cooling, rather than operating continuously at full speed. Significant energy savings can be achieved beyond this technique through fan efficiency increase. Optimizing the motor and electronic driver, increasing fan aerodynamic efficiency through careful redesign, and optimizing fan-system integration are three ways of achieving this.”

Read more about the techniques for achieving efficiency at https://www.qats.com/cms/wp-content/uploads/2015/03/Designing_Efficient_Fans_for_Electronics_Cooling
_Applications.pdf
.

CLICK HERE FOR PART II.

To learn more about Advanced Thermal Solutions, Inc. consulting services, visit www.qats.com or contact ATS at 781.769.2800 or ats-hq@qats.com.

How to Design Efficient Fans for Electronics Cooling Applications

In modern day equipment racks, the power consumed by the cooling fans represents a significant percentage of the overall system power budget. With the advent of data centers and their large energy costs, the issue of “cooling power” is exacerbated. It is, therefore, becoming crucial to design and implement methods for reducing data centers’ power consumption. The Qpedia article, “Designing Efficient Fans for Electronics Cooling Applications,” presents a review of methods available for reducing energy consumption through increasing fan efficiency. Three main ways of improvement by optimization will be discussed: motor and electronic driver optimization, fan aerodynamic optimization and surrounding inlet/outlet equipment optimization. fan

 

How System Flow Affects Fan Sink Performance

Cooling fans consist of an aggregate of airfoils, i.e. blades, positioned around a hub that is driven by an electric motor. Due to their airfoil nature, a pressure differential is required across the blades to create the required flow. Therefore, if this pressure differential is disturbed, fan will suffer performance degradation.

Because air cooling is the most desired method for the thermal management of electronics equipment, fans are used extensively. Applications range from a simple projector to a sophisticated computer. The use of fans in such fluid dynamically complex geometries must be well understood. Equally important is the interaction of the fan with its environment, which will determine its effectiveness as an air mover.

There is much that impacts fan performance. The list includes entrance and exit geometries, size and location of the plenum, its placement in the system, effects of swirl in the air flow, altitude, etc. One area that is not accurately studied, and is continually faced in electronics systems, is the effect of parallel flow over the fan hub.

As mentioned, fans are formed from a series of airfoils. A flow going over the fan hub may impact the pressure differential across the blade that is necessary for the fan to operate properly. This article reports the results of an  experimental investigation for a fan sink that is commonly used in electronics such as PCs and servers.

Fan sinks are commonly used in electronics systems to deliver direct air to devices that need additional cooling. Fans are pressure driven devices, and peripheral flow around them, specifically over the fan blades, may impact their performance. To determine the effect of such system by-pass flow over a fan hub, we considered the fan sink shown in Figure 1. This fan sink is used for cooling a microprocessor and its integral power supply. Our objectives were to determine the air flow of the fan sink, with and without the power supply (blockage), and to evaluate the effect of main stream flow on the fan sink’s performance.

Experimental Procedure

The fan sink was set up in a research-standard wind tunnel allowing the main stream air flow to course over the hub of the fan. This is similar to a typical 1U chassis, where system fans move the air from the rear to the front and the CPU is directly cooled by a dedicated fan sink. A high performance hot wire anemometer (HWA)was used for mapping the flow field in the exhaust of the heat sink. This was done with and without the presence of the CPUs integral power supply. The locations of the velocity probe are shown in Figures 2, 3, and 4.

Positions 0, 1, and 2 (Figure 2) are normal to the planar area of the fan sink, and A, B, C, and D (Figure 3) are along the exhaust area of the unit. Positions A and D were set at the first and last opening of the heat sink, and B and C were 1/3 and 2/3 the distance from the edge, respectively. For all tests, the velocity probe was placed at the halfway point between the heat sink exhaust and the edges of the heat sink, as shown in Figures 2 and 4. This corresponds to positions 0, 1, and 2 in Figure 2 and position 2 in Figure 4. This configuration enabled us to map out the velocity profile in the exhaust of the fan sink at 12 different locations, four positions from left to right (A-D) and three positions top-to-bottom (0-2).

The fan was powered at the nominal 5 volts, consistent with the actual application. The parallel flow was set at four conditions. The first was no flow (V = 0), which established the reference point for this study. Then, the wind tunnel was set at V= 0.5, 1.5, and 3 m/s (100, 300, and 600 ft/min), while measuring at 15 cm upstream of the fan sink assembly. The fan sink was positioned where 0.5 to 3 m/s of flow would pass by its hub while it operated at its nominal condition. Because a fan is a pressure-driven device, it was expected that the flow bypass would adversely impact its performance. At every point of observation, the velocity was measured for two minutes at the rate of two samples per second, resulting in an uncertainty level of + 0.9%.

Results

Table 1 shows the averaged data for velocity and mass flow rate, with and without the power supply in place. The effect of the bypass flow on the fan sinks performance was quantified by comparing the mass flow rates at different velocities. Depending on the magnitude of the system velocity, (i.e. parallel flow) the data shows that the mass flow rate required for cooling the device can be reduced by more than 60.4%.

Figure 5 shows the raw velocity data for all positions measured. Figure 6 shows the velocity data at vertical position 2 and the 4 horizontal positions for the blocked and unblocked cases. It is noteworthy that in both cases the exhaust flow is highly non-uniform. The mass flow rate was calculated based on the open cross-sectional area of the fan sink assembly. The area for the unit with and without the power supply was 0.32×10-3 m2 and 0.13×10-3 m2, respectively.

Observations

The following observations were made as the result of this experimental investigation:

-The fan sink exhibits uneven flow across its exhaust where the power supply resides, as seen in Figures 5 and 6. This may adversely impact the thermal performance of the power supply, depending on its power distribution.

-The uneven flow distribution was observed for both cases (with or without the power supply). Hence, it is attributed to the design of the fan sink rather than the system flow condition alone. For this reason, it is prudent to characterize any fan sink before its implementation in the system.

-Because of the uneven flow distribution, the layout of the component power supply must be carefully considered. The available mass flow rate for cooling is approximately 0.25×10-3 kg/sec.

-The increase in velocity (approximately 20% to 100%) when the power supply is placed in the exhaust of the fan sink is attributed to area reduction.

The mass flow rate is the true measure of available coolant for the power supply, not the air velocity alone. Any obstruction in the intake or exhaust of the fan, e.g. neighboring components in the board layout, must be carefully considered as their presence will impact the performance of the fan sink.

-The flow bypass adversely impacts the performance of the fan sink. The data show 0% reduction in air velocity when the bypass flow is 3 m/sec (with the power supply in place). Additional clogging of the fan sink from dust and other debris will further diminish its performance.

The adverse effect of system flow bypass on the fan sink suggests that system implementation of the fan sink should be carefully considered at the board and system levels. At the very least, the selection (for size) and position of the adjacent components should be carefully considered because the measurement shows that any near vicinity obstacle has a direct impact on the fan’s performance. As we design fan trays with sufficient plenum for the fan to freely exhaust, board level implementation of the fan sink requires similar consideration.

Although detailed flow measurements were taken to characterize the fan sink, the result may not explicitly determine the thermal performance of the power supply and microprocessor. The non-uniformity of the exhaust air from the fan sink suggests that, depending on the heat sink material and the devices power concentration, the heat sink base temperature may be highly non-isothermal. Because fan sinks are used for direct cooling of certain devices, this non-uniformity may adversely impact the thermal management of the device.  The combination of spreading resistance between the fan sink and the device, and the non-uniformity of the exhaust air and the system bypass flow on the fans performance, may render the fan sink inadequate for a given cooling application.

The data suggests that although fan sinks are attractive cooling options, their implementation in a system environment may be more complicated and requires additional investigation. Simply placing a fan sink on top of a hot device may not provide the desired cooling that the engineer envisioned. Therefore, it is strongly recommended not only to carefully quantify system flow bypass on the fan sink, but to also make the proximity of components neighboring the fan sink a point of consideration in the design cycle.

Performance Differences between Fan Types Used for Electronics Cooling

Billions of fans are now in use for active cooling of PCBs and other hot electronic components. An article in Qpedia, the thermal e-magazine from Advanced Thermal Solutions, Inc., (ATS), explores the two most common types of fans used in electronics cooling: the radial (or centrifugal) fan and the axial fan.

The difference between the axial fan and radial fans can be divided into two parts, namely geometry and fluid dynamics.

An axial-flow fan has blades that force air to move in a parallel direction to the shaft around which the blades rotate. For a radial fan, the air flows in on a side of the fan housing, then turns 90 degrees and accelerates, due to centrifugal force as it exits the fan housing. These differences in air flow direction have design implications. For example, a radial fan can blow air across a PCB more efficiently, and use less space, than mounting an axial fan to blow air down onto a board.

The fluid flow rate through an electronics system, e.g., enclosure, is determined by the intercept between the fan and system curves that plot the air pressure drop over volumetric flow rate. A system’s air flow curve can be calculated using 1D fluid mechanics, or it may require the use of high performance CFD or experimental data. In general, for the same power and rotation speed, the radial fan can achieve a higher pressure head than an axial fan. However, an axial fan can achieve a higher maximum flow rate than a radial fan.

In theory, this same approach applies when using two fans in series or in parallel. When the fans are in series, the maximum flow rate should stay the same as for the single fan, but the maximum pressure head doubles. When using two fans in parallel, the maximum pressure head should remain the same as for the single fan, but the flow rate doubles. In real situations, though, the fans may interfere with each other, thus providing lower than expected results. Thus, actual experimentation is typically needed.

Download the Full ATS White Paper Performance Differences Between Fans and Blowers and Their Implementation