Liquid Cooled Heat Sinks

Liquid Cooled fanSINKS

LQHS - Liquid Cooled Heat Sink

For cooling high heat components, LQHS heat sinks combine an active fan mounted to a heat spreading base with internal channels of flowing coolant.With the liquid assist, LQHS heat sinks provide thermal performance at least three times higher than fan-assisted heats sinks without liquid loops.

LQHS heat sinks are combined with pumps and coolant reservoirs to provide continuous, high-level cooling of hot CPUs, GPUs, FPGAs, and AI processors, along with IFBT, MOSFETs and DC-DC converters. For even higher cooling levels, a heat exchanger can be added to the liquid-cooling configuration. ATS provides recommendations for (non-included) fans per user application.


Product Specifications
  • Internal Diameter: 4.826 mm Outside Diameter 6.35 mm Tube Length: 488.5 mm
  • Pin fin heat sinks are anodized black
  • Sizes of 84.00x84.00 mm and 84.00 mm
  • Heights of 25.80 mm and 30.80 mm
  • Tubes are copper
  • Stainless steel screw fan attachment ensures dependable long-term fan to heat sink assembly. 4-40 thread screws are supplied in 4 lengths (1/2”, 3/4”,7/8”, 1”).
  • Fan assembly hole pattern is 50.0 mm C-C (center to center)
  • Includes Thermal Interface Material (TIM) centered on base.
  • Recommended through hole size in PCB is 3.00 mm
Applications
  • CPU, GPU, FPGA or AI Processor cooling
  • Cooling of Mosfets, DC-DC converters
  • IGBT cooling
  • Small industrial laser cooling
  • Cooling of AI-Personal Computers
  • Edge Compute Server Cooling

Thermal Resistance Comparison of Similar Heat Sinks: Liquid Cooled vs. Air Cooled

LQHS
Additional Features
  • Thermal performance is at least 3x better than the exact same size fanSINK without the liquid loop.
  • Integrated HEX, hence, the liquid loop may require one less component.
  • LQHS' thermal performance is equal or better than the same size cold plate with the same fluid flow rate
  • Its performance is equal or better than to the same heat sink with vapor chamber
  • Fluid Types: Water, Propylene Glycol, Refrigerants, Dielectrics, Mineral Oil, EG Mixtures
  • Fan not included please see table of suggested fans for each part number
Application Examples
Example Liquid Loop Configurations and Components
application

This configuration relies on the LQHS' integrated heat exchanger. This reduces the cost and complexity of this liquid cooling solution and features a thermal resistance of 0.05°C/W.

application

For very high heat applications, a heat exchanger can be included in the liquid loop. This will with This configuration relies on the LQHS' integrated heat exchanger. This reduces the cost and complexity of this liquid cooling,

Example Products for LQHS Liquid Loop
  • reciver
    Reservoir

    XSPC Dual 5.25" Acrylic

  • reciver
    Second Heat Exchanger

    ATS HE-54

  • Connectors
    Connectors

    John Guest Polypropylene Equal Straight Connector 1/4

  • Pumps
    Pumps

    Thomas 1420

  • Coolant_Pump
    Coolant Pump

    Bosch PAD2 Electric Coolant Pump

All non-ATS products are examples only and do not reflect a recommendation for these products
L=Length (mm);W=Width (mm); H=Height (mm);T=Thickness (mm); R=Thermal Resistance (°C/W); dP=Pressure (psi);GPM=Gallons per minute;LPM=Liters per minute;
ATS Liquid Cooled Heat Sinks Family (Thermal Resistance With Orion Fan)
Part Number Lifecycle
Status
 
Dimension (mm)Flow Rate
LPM(GPM) 1.9(0.5)
Flow Rate
LPM(GPM) 3.7(1.0)
Flow Rate
LPM(GPM) 5.7(1.5)
Flow Rate
LPM(GPM) 7.6(2.0)
DatasheetCADRoHSCheck
Stock
L W H R
(°C/W)
 
dP
kPA
(psi)
 
R
(°C/W)
 
dP
kPA
(psi)
 
R
(°C/W)
 
dP
kPA
(psi)
 
R
(°C/W)
 
dP
kPA
(psi)
 
ATS-LQHS-74025-C1-R0 ACTIVE 74 74 25.8 0.13 3
(0.44)
0.122 13
(1.89)
0.116 27
(3.92)
0.114 47
(6.82)
Check Stock »
ATS-LQHS-74030-C1-R0 ACTIVE 74 74 30.8 0.13 3
(0.44)
0.122 13
(1.89)
0.116 27
(3.92)
0.114 47
(6.82)
Check Stock »
ATS-LQHS-84025-C1-R0 ACTIVE 84 84 25.8 0.06 10
(1.45)
0.05 36
(5.22)
0.05 77
(11.17)
0.05 134
(19.43)
Check Stock »
ATS-LQHS-84030-C1-R0 ACTIVE 84 84 30.8 0.06 10
(1.45)
0.05 36
(5.22)
0.05 77
(11.17)
0.05 134
(19.43)
Check Stock »
  • Sort Ascending
  • Sort Descending
  • Clear Sorting
  • Columns
Complete Your Liquid Loop with ATS

ATS has the products needed to design a complete liquid cooling loop : iCDMs (Industrial Cooling Distribution Modules), Tubed and High Performance Cold Plates to transfer and remove the heat from the source; Heat Exchangers to transfer heat from the liquid to the air with or without a fan; Chillers to circulate and condition the fluid in the system, Compact Refrigeration Modules for very high capacity cooling. In addition , ATS offers Flow Meters to measure the volumetric flow rate of the fluid in the system and Leak Detectors to notify users of any leaks in the system.