L=Length (mm);W=Width (mm); H=Height (mm);T=Thickness (mm); R=Thermal Resistance (°C/W); dP=Pressure (psi);GPM=Gallons per minute;LPM=Liters per minute;
ATS Liquid Cooled Heat Sinks Family (Thermal Resistance With Orion Fan)
Part Number Lifecycle
Status
 
Dimension (mm)Flow Rate
LPM(GPM) 1.9 (0.5)
Flow Rate
LPM(GPM) 3.7 (1.0)
Flow Rate
LPM(GPM) 5.7 (1.5)
Flow Rate
LPM(GPM) 7.6 (2.0)
DatasheetCADRoHSCheck
Stock
L W H R
(°C/W)
 
dP
kPA
(psi)
 
R
(°C/W)
 
dP
kPA
(psi)
 
R
(°C/W)
 
dP
kPA
(psi)
 
R
(°C/W)
 
dP
kPA
(psi)
 
ATS-LQHS-74025-C1-R0 ACTIVE 74 74 25.8 0.13 3
(0.44)
0.122 13
(1.89)
0.116 27
(3.92)
0.114 47
(6.82)
Check Stock »
ATS-LQHS-74030-C1-R0 ACTIVE 74 74 30.8 0.13 3
(0.44)
0.122 13
(1.89)
0.116 27
(3.92)
0.114 47
(6.82)
Check Stock »
ATS-LQHS-84025-C1-R0 ACTIVE 84 84 25.8 0.06 10
(1.45)
0.05 36
(5.22)
0.05 77
(11.17)
0.05 134
(19.43)
Check Stock »
ATS-LQHS-84030-C1-R0 ACTIVE 84 84 30.8 0.06 10
(1.45)
0.05 36
(5.22)
0.05 77
(11.17)
0.05 134
(19.43)
Check Stock »
  • Sort Ascending
  • Sort Descending
  • Clear Sorting
  • Columns
Complete Your Liquid Loop with ATS

ATS has the products needed to design a complete liquid cooling loop : iCDMs (Industrial Cooling Distribution Modules), Tubed and High Performance Cold Plates to transfer and remove the heat from the source; Heat Exchangers to transfer heat from the liquid to the air with or without a fan; Chillers to circulate and condition the fluid in the system, Compact Refrigeration Modules for very high capacity cooling. In addition , ATS offers Flow Meters to measure the volumetric flow rate of the fluid in the system and Leak Detectors to notify users of any leaks in the system.