• Check Stock
  • Language Icon
  • My Cart My Cart
  • Sign in

ATS-AIC-1016

*Image above is for illustration purpose only..
ATS-AIC-1016
AI Chip Coolers / Direct Liquid Cooling Cold Plate

The ATS-AIC-1016 is a high-performance DLC cold plate built for next-generation AI and high-power compute platforms. Featuring a robust multi-material construction and integrated thermal interface solution, it provides dependable liquid cooling in demanding environments.

Features & Benefits
  • Designed for NVIDIA Blackwell GPU platforms
  • Aluminum cold plate with copper heat spreader
  • Integrated T766 thermal interface material
  • Thermal resistance down to 0.024 °C/W (at 6 LPM)
  • Supports up to 2 kW thermal design power
  • Dimensions: 99 × 99 × 36 mm
  • Robust build for high-power AI operation
  • Universal barb fittings for 8 mm OD / 5 mm ID tubing
  • Weight: 771 g for enhanced structural stability
Applications
  • AI training accelerators and high-power GPUs
  • Advanced HPC processors and computer platforms
  • High-density AI racks using direct-to-chip cooling
  • Next-generation and custom AI hardware designs
Specifications
Part Number Lifecycle
Status
Plate Dimension (mm) Weight (gr) Material Flow Rate
LPM(GPM) 1.0 (0.26)
Flow Rate
LPM(GPM) 2.0 (0.52)
Flow Rate
LPM(GPM) 3.0 (0.79)
Flow Rate
LPM(GPM) 4.0 (1.05)
Length Width Height R
(°C/W)
dP
kPA (psi)
R
(°C/W)
dP
kPA (psi)
R
(°C/W)
dP
kPA (psi)
R
(°C/W)
dP
kPA (psi)
ATS-AIC-1016 ACTIVE 99.2 99.0 36.0 771 Al / Cu 0.035 2.21 (0.32) 0.03 9.17 (1.33) 0.028 20.82 (3.02) 0.026 36.89 (5.35)
Thermal Performance
Schematic Image Thermal Resistance
Flow Rate
LPM(GPM)
R
(°C/W)
dP
kPA (psi)

*Image above is for illustration purpose only.
1.0 (0.26) 0.035 2.21 (0.32)
2.0 (0.52) 0.03 9.17 (1.33)
3.0 (0.79) 0.03 (0.00) 20.82 (3.02)
4.0 (1.05) 0.026 36.89 (5.35)
5.0 (1.32) 0.025 57.23(8.3)
6.0 (1.58) 0.024 81.77(11.86)
ATS-AIC-1016    (Data Sheet)
download data sheet
ATS-AIC-1016
CAD MODEL (Fused Model) - use for Form and Fit
Download CAD Model (Fused Model) (used for Form and Fit use)
RoHS & REACH Certificate download data sheet
Complete Your Liquid Loop with ATS

ATS has the products needed to design a complete liquid cooling loop : iCDMs (Industrial Cooling Distribution Modules), Tubed and High Performance Cold Plates to transfer and remove the heat from the source; Heat Exchangers to transfer heat from the liquid to the air with or without a fan; Chillers to circulate and condition the fluid in the system, Compact Refrigeration Modules for very high capacity cooling. In addition , ATS offers Flow Meters to measure the volumetric flow rate of the fluid in the system and Leak Detectors to notify users of any leaks in the system.