CDU-X

*Image above is for illustration purpose only..
CDU-X
Floor-mount Cooling Distribution Module

The ATS CDU–X is a floor–mount, high–capacity Coolant Distribution Unit engineered to deliver continuous 4 MW of precise single–phase cooling for today's most demanding data center and industrial systems.

Combining robust mechanical design, intelligent PLC control, and reliable dual–redundant operation, the CDU-X provides efficient, monitored, and service–ready thermal management for AI clusters, HPC servers, and high–power electronics.

Features & Benefits
  • Massive Cooling Power —Provides up to 4 MW of single–phase liquid cooling for high–density data center and industrial applications.
  • Rugged Construction —Heavy–duty structural–steel chassis with powder–coat finish ensures long–term durability and corrosion resistance.
  • Advanced Thermal Control —Motorized valves and liquid–to–liquid heat exchanger deliver intelligent and precise temperature and flow regulation.
  • High Flow Capacity —Achieves up to 1,600 LPM with a 200 psi pump head for stable performance under demanding thermal loads.
  
  • Intelligent PLC System —Integrated PLC and HMI touchscreen provide real–time monitoring, automated control, and Ethernet remote access.
  • Built–In Redundancy —Dual pumps, PLC, and power supplies maintain uninterrupted cooling during maintenance or fault conditions.
  • Comprehensive Safety —Includes over–temperature, over–pressure, low–flow, leak, and emergency–shutdown protection.
  • Service–Friendly Design —Replaceable strainer filter and variable–speed pump control allows efficient, on–the–fly maintenance and optimized power use.
Applications
  • AI and HPC compute racks
  • Immersion-cooled server banks
  • High-density data centers
  • Industrial power electronics cooling
  • Mission-critical test systems and energy storage modules
 
Specifications
L= Length; W=Width; D= Diameter;WT=Weight(kg); CC= Cooling Capacity; CFR=Coolant Flow Rate; RV= Reservoir Volume ; FC=Fluid Connections; PIC= Power Input Current; OE=Operating Environment; OHR= Operating Humidity Range;
Part NumberDIMENSIONS (mm)WTCCCFRRVFCPICOEOHR
LWD
CDU-X 2700 1600 1600 2,200 Kg 4,000 kW
(4 MW)
1,600 LPM
(422.7 GPM)
100 L
(26.4 Gal)
4 "sanitary flanges
(4 ports)
100 A 10–30°C
(50–86°F)
0–90% RH
Complete Your Liquid Loop with ATS

ATS has the products needed to design a complete liquid cooling loop : iCDMs (Industrial Cooling Distribution Modules), Tubed and High Performance Cold Plates to transfer and remove the heat from the source; Heat Exchangers to transfer heat from the liquid to the air with or without a fan; Chillers to circulate and condition the fluid in the system, Compact Refrigeration Modules for very high capacity cooling. In addition , ATS offers Flow Meters to measure the volumetric flow rate of the fluid in the system and Leak Detectors to notify users of any leaks in the system.