CDU-RM250

Liquid Cooling iCDM CDU-RM250
*Image above is for illustration purpose only..
CDU-RM250
Rack-mount Coolant Distribution Unit

The ATS CDU-RM250 is a high-performance rackmount Coolant Distribution Unit designed to provide up to 235 kW of precise, single-phase liquid cooling for rack-level and modular data center applications. Compact yet powerful, the 4U CDU-RM250 enables efficient liquid-to-liquid heat exchange between facility water loops and IT or electronic cooling loops, delivering exceptional thermal control in a minimal footprint.

Featuring two 48 VDC pumps, PLC-based control, and HMI interface, it offers intelligent operation and full visibility of system performance. Dual redundant pumps and power supplies ensure uninterrupted uptime, while advanced monitoring safeguards against thermal or flow anomalies.

Fabricated from powder-coated aluminum and built for continuous operation, the CDU-RM250 brings enterprise-grade cooling performance directly to the rack.

Features & Benefits
  • Compact Power: 4U rack-mount design delivering up to 235 kW of liquid cooling with 150 LPM facility flow rate at an approach of temperature of 9°C.
  • High Efficiency:Liquid-to-liquid heat exchanger for stable, low-loss thermal transfer.
  • Smart Control:PLC + HMI provide intelligent management and real-time visibility.
  • Reliable Operation:Dual redundant pumps and power supplies ensure uninterrupted cooling.
  
  • Flexible Integration:Designed for seamless connection to facility water loops.
  • Quiet and Efficient:Low-noise, variable-speed pump minimizes energy use.
  • Durable Build:Lightweight, powder-coated aluminum chassis for long-term performance.
  • Maintenance-Friendly:Simplified service design with no filter change requirements.
Applications
  • Cold plate and heat exchanger performance testing
  • Electronics and power-device cooling
  • Immersion cooling evaluation and fluid loop testing
  • Laboratory and industrial R&D setups
  • Portable or auxiliary cooling where facility water is unavailable
 
Specifications
H=Height; W=Width; D=Diameter;WT=Weight(kg); MCC=Maximum Cooling Capacity; CFR=Coolant Flow Rate; RV=Reservoir Volume ; FC=Fluid Connections; PIC=Power Input Current; OE=Operating Environment; OHR=Operating Humidity Range;
Part NumberDIMENSIONS (mm)WTMCCCFRRVFCPICOEOHR
HWD
ATS-CDU-RM250 177.8 482 1186 65 kg 235 kW 137 LPM
(36.2 GPM)
7 L
(1.8 Gal)
1" sanitary flanges
(4 ports)
11 A/115 VAC or 5.5A/230 VAC 4–40°C
(39.2–104°F)
0–90% RH
Complete Your Liquid Loop with ATS

ATS has the products needed to design a complete liquid cooling loop : iCDMs (Industrial Cooling Distribution Modules), Tubed and High Performance Cold Plates to transfer and remove the heat from the source; Heat Exchangers to transfer heat from the liquid to the air with or without a fan; Chillers to circulate and condition the fluid in the system, Compact Refrigeration Modules for very high capacity cooling. In addition , ATS offers Flow Meters to measure the volumetric flow rate of the fluid in the system and Leak Detectors to notify users of any leaks in the system.