ATS-TCP-1004
Tubed Cold Plates

The Tubed Cold Plate family is engineered as a cost effective and reliable solution for thermal management applications where liquid cooling of components is preferred over air.

The cold plates are manufactured in the USA using continuous copper or stainless steel tubing. The stainless steel tubing is secured between two base plates. The copper tubing uses a press-fit attachment method that maximizes heat transfer since the tubes are directly connected to the plate instead of through a bulky epoxy or other material that can act as thermal insulator.

Features & Benefits
  • Cost-effective thermal management solution for component cooling where the heat load is low to moderate
  • Compatible with industry accepted coolants
  • The cold plate base is made of aluminum 6063
  • Copper tubed cold plates feature a direct, press fit attachment method to provide superior heat transfer
  • Stainless steel tubed cold plates feature stainless steel tubing (SS 304/316) secured between two plates
  • Supplied with secure, 3/8" push-to-connect tube fittings for a tight connection between the cold plate and inlet and outlet tubing.
  • Tube outer diameter is 3/8" (9.525 mm).
  • Maximum pressure: 200 psi
  • Plastic tubing connecting to our Cold Plate fitting has to be at least 90 durometer Shore A scale

Applications

  • Automotive
  • Instruments
  • Uninterruptible Power Supplies
  • Wind Turbines
  • Photovoltaic Inverters
  • Induction Heaters
  • Motor Devices
Product Details
Part Number Lifecycle
Status
Plate Dimension (mm) Overall
Length
(mm)
# No
of Tube
Pass
Tube
Material
Flow Rate
LPM(GPM) 1.9(0.5)
Flow Rate
LPM(GPM) 3.7(1.0)
Flow Rate
LPM(GPM) 5.7(1.5)
Flow Rate
LPM(GPM) 7.6(2.0)
Length Width Height R
(°C/W)
dP
kPA (psi)
R
(°C/W)
dP
kPA (psi)
R
(°C/W)
dP
kPA (psi)
R
(°C/W)
dP
kPA (psi)
ATS-TCP-1004 ACTIVE 305.0 178.0 15.0 393 6 Copper 0.011 6.62 (0.96) 0.006 22.2 (3.22) 0.005 45.9 (6.66) 0.004 77.56 (11.25)
Thermal Performance
Schematic Image Thermal Resistance
Flow Rate
LPM(GPM)
R
(°C/W)
dP
kPA (psi)

*Image above is for illustration purpose only.
1.9(0.5) 0.011 6.62 (0.96)
3.7(1.0) 0.006 22.2 (3.22)
5.7(1.5) 0.005 45.9 (6.66)
7.6(2.0) 0.004 77.56 (11.25)
ATS-TCP-1004    (Data Sheet)
download data sheet
ATS-TCP-1004
Mechanical Drawing - FUSED MODEL (used for Form and Fit use)
download fused Model for Form and Fit use
RoHS & REACH Certificate download data sheet
Complete Your Liquid Loop with ATS

ATS has the products needed to design a complete liquid cooling loop : iCDMs (Industrial Cooling Distribution Modules), Tubed and High Performance Cold Plates to transfer and remove the heat from the source; Heat Exchangers to transfer heat from the liquid to the air with or without a fan; Chillers to circulate and condition the fluid in the system, Compact Refrigeration Modules for very high capacity cooling. In addition , ATS offers Flow Meters to measure the volumetric flow rate of the fluid in the system and Leak Detectors to notify users of any leaks in the system.